Customization: | Available |
---|---|
Breaking Capacity: | Low Voltage Circuit Breakers |
Operation: | Energy-storage Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No.
|
Description
|
Technical parameters
|
|||
1
|
Rated voltage, kV
|
72.5
|
126
|
145
|
252
|
3
|
Rated frequency, Hz
|
50/60
|
|||
4
|
Rated current, A
|
1600~4000
|
3150~4000
|
||
|
1min Power frequency withstand voltage
|
140
|
230
|
265
|
460
|
|
Lightning impulse withstand voltage
|
325
|
550
|
650
|
1050
|
5
|
Rated short-circuit breaking
current, kA |
25~40
|
40~63
|
||
7
|
Rated short circuit breaking
current (peak), kA |
63~ 100
|
100~ 157.5
|
||
8
|
Rated short duration, s
|
3
|
3
|
3
|
3
|
|
Rated out-of-phase breaking current
|
10
|
10
|
10
|
10
|
|
Rated cable(line) charging
breaking current |
10
|
31.5
|
50
|
125
|
|
Rated gas pressure, Mpa
|
0.4
|
0.5
|
0.5
|
0.6
|
|
Operation sequence
|
O-0.3s-CO- 180s-CO
|
|||
|
SF6 gas leakage rate (per year)
|
≤1%
|
|||
14
|
First of several genes
|
1.5
|
1.55
|
1.5
|
1.3
|
|
Main loop resistance, μΩ
|
≤40
|
≤45
|
≤45
|
≤50
|
|
Heater voltage
|
AC220
|
|||
|
Control circuit and signal circuit voltage
|
DC220, DC230
|
|||
|
Motor voltage
|
DC220, DC230
|
Description
Outdoor Sulfur Hexafluoride (SF6) dead tank circuit breakers,
Circuit breakers meet the requirements specified in EN 62271-1, EN 62271-100, EN 60273, and other relevant EN (IEC) standards.