Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class

Product Details
Customization: Available
Application: Power, Electronic, Instrument, Lighting, Rectifier
Phase: Three
Diamond Member Since 2024

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Importers and Exporters
The supplier has import and export rights
Quality Assurance
The supplier provides quality assurance
to see all verified strength labels (15)
  • Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
  • Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
  • Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
  • Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
  • Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
  • Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
Find Similar Products
  • Overview
  • Detailed Photos
Overview

Basic Info.

Model NO.
ZBWS-M-1500/33
Cooling Method
Oil-immersed Type Transformer
Winding Type
Two-winding Transformer
Certification
ISO9001
Usage
Single-phase Transformer, Rectifier Transformer, Combined Transformer, Power Transformer, Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
EE
Brand
Vouchinvan
Transformer Type
Oil Immersed
Rated Capacity
up to 20000kVA
Rated Voltage
up to 36kv
Frequency
50/60Hz
Hv Bushing
Dead Front or Loop Feed Designs
LV Bushing
Epoxy or Porcelain Bushing
Winding Material
Copper /Aluminum
Vector Group
Dyn11, Dyn5
Cooling
Onan/ Onaf
Tap Changer
Yes
Transport Package
Wooden Case
Specification
16000kva
Trademark
Vouchivan
Origin
Xuzhou, China
HS Code
85042100

Product Description


Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
Product Introduction
This 1600 kVA prefabricated substation was delivered to Ethiopia in 2022. It's used in factories that manufacture electrical products. This prefabricated substation (also known as compact transformer) contains HV and LV switchgear panels with distribution transformer to provide comprehensive solution. This prefabricated substation is ease of transportation and ready to relocate, ready for installation and commissioning, compact and robust design, equipped with high quality HV and LV equipment, wide range of factory designed options, reliable and minimal maintenance.
 
The rated power of the Oil type distribution transformer is 1600 kVA with ONAN cooling, 3 phase, the primary voltage is 33kV with ±2*2.5% tapping range(NLTC), the secondary voltage is 0.4kV, they formed a vector group of Dyn5.
 
Our 1600 KVA prefabricated substation was designed with advanced technology and adopts high quality material and components which result in reliable quality and long operation time.
We ensure that each one of our delivered units has undergone rigorous full acceptance testing. We provide one-package service from consulting, quoting, manufacturing, installation, commissioning, training to after sale services, our products are now operating in more than 50 counties in the world. We aim to be your most reliable supplier as well as your best partner in business!
 

Scope of Supply

Product: Prefabricated substation
Rated Power: Up to 1600 KVA
Primary Voltage: Up to 35 KV
 

Technical Specification
1600 KVA prefabricated substation specifications type and data sheet
 
Delivered to Ethiopia
Year 2022
Model YBM-33/0.4-1600
Type Prefabricated substation
Standard IEC62271
Rated Power 1600 kVA
Frequency 50 HZ
Phase Three
Cooling Type ONAN
Rated Voltage 33/0.4 kV
 
1600 KVA distribution transformer specifications type and data sheet

 
Delivered to Ethiopia
Year 2022
Model S-M-1600 kVA-33/0.4kV
Type Oil type distribution transformer
without conservator
Standard IEC60076
Rated Power 1600 kVA
Frequency 50 HZ
Phase Three
Cooling Type ONAN
Primary Voltage 33 kV
Secondary Voltage 0.4 kV
Winding Material Copper
Vector Group Dyn5
Impedance 6%
Tap Changer NLTC
Tapping Range ±2*2.5%
No Load Loss ≤1380 KW
On Load Loss ≤15400 KW
Accessories Standard Configuration
Remarks N/A


1600 kVA-33/0.4kV Prefabricated Substation Drawing
1600 kVA prefabricated substation diagram drawing and size.

 
Distribution transformer diagram drawing

Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv ClassOutline dimensional drawing

Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class

Single line diagram
Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class

Our pad mounted transformer was designed with advanced technology and adopts high quality material and components which result in reliable quality and long operation time.

 

We ensure that each one of our delivered units has undergone rigorous full acceptance testing. We provide one-package service from consulting, quoting, manufacturing, installation, commissioning, training to after sale services, our products are now operating in more than 50 counties in the world. We aim to be your most reliable supplier as well as your best partner in business!
 

 


Routine test

-Measurement of winding resistance
-Measurement of voltage ratio and check of phase displacement
-Measurement of short-circuit impedance and loss
-Measurement of no-load loss and current
-Dielectric routine tests
-Tests on on-load tap-changers, where appropriate
-Leak testing with pressure for liquid-immersed transformers(tightness test)
-Tightness tests and pressure tests for tanks for gas-filled transformers
-Check of the ratio and polarity of built-in current transformers
-Check of core and frame insulation for liquid immersed transformers with core or frame insulation

Type test

-Temperature-rise type test
-Dielectric type tests
-Determination of sound level for each method of cooling for which a guaranteed sound level is specified
-Measurement of the power taken by the fan and liquid pump motors
-Measurement of no-load loss and current at 90% and 110% of rated voltage

Special test

-Dielectric special tests
-Winding hot-spot temperature-rise measurement
-Determination of capacitances windings-to-earth, and between windings
-Measurement of dissipation factor(tanδ) of the insulation system capacitances
-Determination of transient voltage transfer characteristics
-Measurement of zero-sequence impedance(s) on three-phase transformers
-Short-circuit withstand test
-Measurement of d.c. insulation resistance each winding to earth and between windings
-Vacuum deflection test on liquid immersed transformers
-Pressure deflection test on liquid immersed transformers
-Vacuum tightness test on site on liquid immersed transformers

Detailed Photos


Power transformer three phase oil immsered electrical transformer rated voltage during 6-35kV, oil immersed transformer are most used in power plant,power grid transmission and distribution station,industry& commerce electrical substation as the electrical equipment of power transmission


1,Two windings or three windings
2,On-load or no-load voltage tapping changer
3,Natural cooling or force air or oil cooling
4,Rated capacity range 30-2500kVA

1600 kVA-33/0.4kV Prefabricated Substation Manufacturing Process

Distribution transformer

Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
HV and LV switchgear panels
Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class


Finished 1600 kVA-33/0.4kV Prefabricated SubstationSpecific Components Transformer Required for Your Application Requirements up to 5mva 33kv ClassSpecific Components Transformer Required for Your Application Requirements up to 5mva 33kv ClassSpecific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
Installation Commissioning and Operation
Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class


Inspection of distribution transformer before operation:

1. Check the transformer certificate; if the certificate exceeds two months, the insulation resistance should be retested.

2. Check the oil level and breathing hole; there should be no oil leakage, oil leakage and good ventilation.

3. Check whether the high and low voltage insulation bushing and relevant lead wires are intact, and whether the screws are loose.

4. Whether the position of the voltage regulating switch is correct and whether the high and low voltage fuses are suitable.

5. Lightning protection shall be complete and grounding resistance shall be measured to be qualified.

6. There should be no abnormal phenomena in cables and busbars.


Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv ClassOUR PAKAGE:

Long time shipment & Seaworthy wooden box

Wooden package optional:
1,choose one unit/ wooden box
2,choose 2unit/ wooden box to save cost

Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
OUR SERVICE:

1,Quick response in before sales period help you got order
2,Excellent service in production time let you know each step we made
3,Reliable quality solve you aftersale headache
4,Long period quality waranty ensure you can buy without hesitate
Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
Vouchivan (VCV) transformer is the top transformer supplier in China.  The factory is located in Jiangsu Province,covering an area of 30,000 square meters.  With more than 20 years of transformer export experience,the professional technical team can meet your requirements for all technical standards;  the professional marketing team will quickly and efficiently promote your transformer project,saving you more time and economic costs.  Various international certifications of transformers to ensure product quality,safety and reliability.  The practical application of VCV Transformer in nearly a hundred countries will make you more confident in VCV Transformer.  VCV Transformer will be your good choice.
Specific Components Transformer Required for Your Application Requirements up to 5mva 33kv Class
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier
People who viewed this also viewed