Customization: | Available |
---|---|
Breaking Capacity: | High Voltage Circuit Breakers |
Operation: | Electric Type |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
No. |
Item |
Unit |
Technical parameter |
Note |
||
1 |
Rated voltage |
kV |
66 |
|
||
2 |
Maximum working voltage
|
kV |
72.5 |
|
||
3 |
Rated current |
A |
3150 |
|
||
4 |
Rated breaking current
|
kA |
40 |
|
||
5 |
Rated closing current |
kA |
100 |
|
||
6 |
closing time
|
ms |
≤150 |
|
||
7 |
Opening time |
ms |
≤30 |
|
||
8 |
Total breaking time |
ms |
≤60 |
|
||
9 |
Operation ondifferent time |
interphase
|
closing |
ms |
≤4 |
|
|
|
|
opening |
ms |
≤2 |
|
10 |
operating mechanism
|
|
CTB Electric spring operating mechanism |
|
||
11 |
Operate the control loop power supply voltage |
V |
DC220/110 |
Description
Outdoor Sulfur Hexafluoride (SF6) dead tank circuit breakers,
Circuit breakers meet the requirements specified in EN 62271-1, EN 62271-100, EN 60273, and other relevant EN (IEC) standards.