Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment

Product Details
Customization: Available
Application: Power, Electronic, Instrument, Lighting, Rectifier
Phase: Three
Diamond Member Since 2024

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Importers and Exporters
The supplier has import and export rights
Quality Assurance
The supplier provides quality assurance
to see all verified strength labels (15)
  • Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
  • Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
  • Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
  • Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
  • Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
  • Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
Find Similar Products
  • Overview
  • Product Description
Overview

Basic Info.

Model NO.
SCB11-250kVA-11/0.4kV
Cooling Method
Oil-immersed Type Transformer
Winding Type
Two-winding Transformer
Certification
ISO9001
Usage
Single-phase Transformer, Rectifier Transformer, Combined Transformer, Power Transformer, Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
EE
Brand
Vouchinvan
Type
Resin Cast Dry Type Transformer
Standard
IEC60076
Cooling Type
an/Af
Winding Material
Aluminum
Vector Group
Dyn11
Impedance
4%
Tap Changer
Nltc
Tapping Range
±2*2.5%
Accessories
Temperature Controller, Cooling Fans
Transport Package
Wooden Case
Specification
250kva
Trademark
Vouchivan
Origin
Xuzhou, China
HS Code
85042100

Product Description


Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
Product Description

Temperature control system
 

Built-in PT100 probes in 3 phase windings to detect the real-time temperature of windings and cycle display them in the digital screen.

Open circuit alarm and fault self-check alarm display and signal output.

3 stages automatically actions while the temperature reached to the set value, 1st stage the cooling fans start automatically, 2nd stage high temperature alarm,3rd stage over temperature trip.

Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical EquipmentFans manual/auto control switch, timing start/stop, history data output.

4-20mA current output

RS485 Modbus communication protocol

Environment temperature measurement

Core temperature measurement


Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment

Dry Type Transformer Advantages:

1. No Fire Hazard

2. Safety for people and property

3. Outage customer costs

4. Ecological and Environmentally Friendly

5. Maintenance & Pollution Free

6. Suited for damp and/or contaminated

7. Excellent resistance to short circuit effect

8. Excellent capacity to support overload

9. Excellent performance toward seismic phenome

10. Saving Costs give lower installation related costs

11. Easy Installation

Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
 
Scope of Supply
 

Product: resin cast dry type transformer

Voltage level: up to 35KV

Rating level: up to 20MVA

The transformer can be designed according to customer's requirements

Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
 

Technical Specification

 
SCB 10 
Rated capacity (KVA) Voltage Combination andTap range Vector group Symbol No-load loss                        (W) Load loss (W) Impedance Voltage(%) No-load current(%)
HV(KV) HVTap range(%) LV(KV)
30 6     6.3     10    10.5   11 ±5%     or ±2*2.5% 0.4 Dyn11 190 710 4.0  2.0 
50 270 1000 2.0 
80 370 1380 1.5 
100 400 1570 1.5 
125 470 1850 1.3 
160 540 2130 1.3 
200 620 2530 1.1 
250 720 2760 1.1 
315 880 3470 1.0 
400 980 3990 1.0 
500 1160 4880 1.0 
630 1300 5960 6.0  0.85 
800 1520 6960 0.85 
1000 1770 8130 0.85 
1250 2090 9690 0.85 
1600 2450 11700 0.85 
2000 3050 14400 0.70 
2500 3600 17100 0.70 
 
SCB 11
Rated capacity (KVA) Voltage Combination andTap range Vector group Symbol No-load loss                        (W) Load loss (W) Impedance Voltage(%) No-load current(%)
HV(KV) HVTap range(%) LV(KV)
30 6     6.3     10    10.5   11 ±5%     or ±2*2.5% 0.4 Dyn11 170 710 4.0  2.0 
50 240 1000 2.0 
80 330 1380 1.5 
100 360 1570 1.5 
125 420 1850 1.3 
160 480 2130 1.3 
200 550 2530 1.1 
250 640 2760 1.1 
315 790 3470 1.0 
400 880 3990 1.0 
500 1040 4880 1.0 
630 1170 5960 6.0  0.85 
800 1360 6960 0.85 
1000 1590 8130 0.85 
1250 1880 9690 0.85 
1600 2200 11700 0.85 
2000 2740 14400 0.70 
2500 3240 17100 0.70 
 
SCB 12
Rated capacity (KVA) Voltage Combination andTap range Vector group Symbol No-load loss                        (W) Load loss (W) Impedance Voltage(%) No-load current(%)
HV(KV) HVTap range(%) LV(KV)
30 6     6.3     10    10.5   11 ±5%     or ±2*2.5% 0.4 Dyn11 150 710 4.0  2.0 
50 215 1000 2.0 
80 295 1380 1.5 
100 320 1570 1.5 
125 375 1850 1.3 
160 430 2130 1.3 
200 495 2530 1.1 
250 575 2760 1.1 
315 705 3470 1.0 
400 785 3990 1.0 
500 930 4880 1.0 
630 1040 5960 6.0  0.85 
800 1215 6960 0.85 
1000 1415 8130 0.85 
1250 1670 9690 0.85 
1600 1960 11730 0.85 
2000 2440 14450 0.70 
2500 2880 17170 0.70 
SCB 13
Rated capacity (KVA) Voltage Combination andTap range Vector group Symbol No-load loss                        (W) Load loss (W) Impedance Voltage(%) No-load current(%)
HV(KV) HVTap range(%) LV(KV)
30 6     6.3     10    10.5   11 ±5%     or ±2*2.5% 0.4 Dyn11 135 640 4.0  2.0 
50 195 900 2.0 
80 265 1240 1.5 
100 290 1410 1.5 
125 340 1660 1.3 
160 385 1910 1.3 
200 445 2270 1.1 
250 515 2480 1.1 
315 635 3120 1.0 
400 705 3590 1.0 
500 835 4390 1.0 
630 935 5360 6.0  0.85 
800 1090 6260 0.85 
1000 1270 7310 0.85 
1250 1500 8720 0.85 
1600 1760 10500 0.85 
2000 2190 13000 0.70 
2500 2590 15400 0.70 

We ensure that each one of our delivered units has undergone rigorous full acceptance testing. We provide one-package service from consulting, quoting, manufacturing, installation, commissioning, training to after sale services, our products are now operating in more than 50 counties in the world. We aim to be your most reliable supplier as well as your best partner in business!
 

Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment


Routine test

-Measurement of winding resistance
-Measurement of voltage ratio and check of phase displacement
-Measurement of short-circuit impedance and loss
-Measurement of no-load loss and current
-Dielectric routine tests
-Tests on on-load tap-changers, where appropriate
-Leak testing with pressure for liquid-immersed transformers(tightness test)
-Tightness tests and pressure tests for tanks for gas-filled transformers
-Check of the ratio and polarity of built-in current transformers
-Check of core and frame insulation for liquid immersed transformers with core or frame insulation

Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
Type test

-Temperature-rise type test
-Dielectric type tests
-Determination of sound level for each method of cooling for which a guaranteed sound level is specified
-Measurement of the power taken by the fan and liquid pump motors
-Measurement of no-load loss and current at 90% and 110% of rated voltage

Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
Special test

-Dielectric special tests
-Winding hot-spot temperature-rise measurement
-Determination of capacitances windings-to-earth, and between windings
-Measurement of dissipation factor(tanδ) of the insulation system capacitances
-Determination of transient voltage transfer characteristics
-Measurement of zero-sequence impedance(s) on three-phase transformers
-Short-circuit withstand test
-Measurement of d.c. insulation resistance each winding to earth and between windings
-Vacuum deflection test on liquid immersed transformers
-Pressure deflection test on liquid immersed transformers
-Vacuum tightness test on site on liquid immersed transformers

 

Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical EquipmentOUR PAKAGE:

Long time shipment & Seaworthy wooden box

Wooden package optional:
1,choose one unit/ wooden box
2,choose 2unit/ wooden box to save cost

Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
OUR SERVICE:

1,Quick response in before sales period help you got order
2,Excellent service in production time let you know each step we made
3,Reliable quality solve you aftersale headache
4,Long period quality waranty ensure you can buy without hesitate
Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
Vouchivan (VCV) transformer is the top transformer supplier in China.  The factory is located in Jiangsu Province,covering an area of 30,000 square meters.  With more than 20 years of transformer export experience,the professional technical team can meet your requirements for all technical standards;  the professional marketing team will quickly and efficiently promote your transformer project,saving you more time and economic costs.  Various international certifications of transformers to ensure product quality,safety and reliability.  The practical application of VCV Transformer in nearly a hundred countries will make you more confident in VCV Transformer.  VCV Transformer will be your good choice.
Higher Load Capacity 250kVA Dry Type Transformer 11/0.4kv for Electrical Equipment
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier